Digital combi
IE23xx
 
IE2300, IE2301, IE2302, IE2310, IE2311, IE2312 | 4 x digital input + 4 x digital output 24 V DC, I<span class="EFF_MAX_subscript">MAX</span> = 0.5 A
IE2300
IE2301
IE2302
IE2310
IE2311
IE2312
Connector
assignment
I/O
connection
8 mm I/O
connection sockets
Signal status display
Labelling areas
Power supply
status display:
Box supply (US)
Auxiliary voltage (UP)
M8
M12
1 | + 24 V DC Us
3 | GND
4 | In-/Output
1 | + 24 V DC Us
2 | In-/Output B
3 | GND
4 | In-/Output A
5 | n.c.
1 | + 24 V DC Us
2 | + 24 V DC UP
3 | GND
4 | GND
3-wire  2-wire
IP-Link interface
Power supply feed
Power supply down-
stream connection
IP-Link interface

IE230x, IE231x | 4 x digital input + 4 x digital output 24 V DC, IMAX = 0.5 A

The IE23xx digital I/O modules combine four digital inputs and four digital outputs in one device. Various filter constants are available for the inputs. The outputs handle load currents of up to 0.5 A, are short-circuit-proof and protected against inverse polarity. The state of each signal is indicated by means of light emitting diodes. The signals are connected optionally via 8 mm diameter snap types (IE2300, IE2310), screw type M8 connectors (IE2301, IE2311) or connector M12 screw type (IE2302, IE2312).

Technical data IE2300 IE2301 IE2302
Number of channels 4 inputs + 4 outputs
Input/output connections 8 mm, snap type M8, screw type M12, screw type
Input filter 3.0 ms
“0“ signal voltage -3…+5 V
“1“ signal voltage 11…30 V, 6 mA input current (EN 61131-2, type 2)
Sensor supply from control voltage, max. 0.5 A total, short-circuit-proof
Load type ohmic, inductive, lamp load
Rated load voltage 24 V DC (-15 %/+20 %)
Max. output current 0.5 A per channel, individually short-circuit-proof
Short circuit current typ. 1.5 A
Auxiliary power current typ. 20 mA per channel
Current consumption from US (without sensor current) 25 mA
Power supply connection feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin
Bit width in the process image 4 inputs + 4 outputs
Electrical isolation channels/control voltage: no, between the channels: no, control voltage/fieldbus: yes, via IP-Link
Operating/storage temperature 0…+55 °C/-25…+85 °C
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 65/66/67 (conforms to EN 60529)/variable
Approvals CE, UL
Technical data IE2310 IE2311 IE2312
Number of channels 4 inputs + 4 outputs
Input/output connections 8 mm, snap type M8, screw type M12, screw type
Input filter 0.2 ms
“0“ signal voltage -3…+5 V
“1“ signal voltage 11…30 V, 6 mA input current (EN 61131-2, type 2)
Sensor supply from control voltage, max. 0.5 A total, short-circuit-proof
Load type ohmic, inductive, lamp load
Rated load voltage 24 V DC (-15 %/+20 %)
Max. output current 0.5 A per channel, individually short-circuit-proof
Short circuit current typ. 1.5 A
Auxiliary power current typ. 20 mA per channel
Current consumption from US (without sensor current) 25 mA
Power supply connection feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin
Bit width in the process image 4 inputs + 4 outputs
Electrical isolation channels/control voltage: no, between the channels: no, control voltage/fieldbus: yes, via IP-Link
Operating/storage temperature 0…+55 °C/-25…+85 °C
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 65/66/67 (conforms to EN 60529)/variable
Approvals CE, UL