Digital output
IE200x
 
IE2000, IE2001, IE2002 | 8-channel digital output 24 V DC, I<span class="EFF_MAX_subscript">MAX</span> = 0.5 A
IE2000
IE2001
IE2002
Connector
assignment
I/O
connection
8 mm I/O
connection sockets
Signal status display
Labelling areas
Power supply
status display:
Box supply (US)
Auxiliary voltage (UP)
M8
M12
1 | + 24 V DC Us
3 | GND
4 | Output
1 | + 24 V DC Us
2 | Output B
3 | GND
4 | Output A
5 | n.c.
1 | + 24 V DC Us
2 | + 24 V DC UP
3 | GND
4 | GND
3-wire  2-wire
Power supply feed
Power supply down-
stream connection
IP-Link interface

IE200x | 8-channel digital output 24 V DC, IMAX = 0.5 A

The IE200x digital output modules connect the binary control signals from the automation unit on to the actuators at the process level. The eight outputs handle load currents of up to 0.5 A and indicate their status through light emitting diodes. The signals are optionally connected via 8 mm snap type (IE2000), M8 (IE2001) or M12 (IE2002) screw type connectors. The outputs are short-circuit-proof and protected against inverse connection.

Technical data IE2000 IE2001 IE2002
Number of outputs 8
Output connections 8 mm, snap type M8, screw type M12, screw type
Load type ohmic, inductive, lamp load
Nominal output voltage 24 V DC (-15 %/+20 %)
Max. output current 0.5 A per channel, individually short-circuit-proof
Short circuit current typ. 1.5 A
Auxiliary power current typ. 20 mA per channel
Current consumption from US (without sensor current) 25 mA
Power supply connection feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin
Bit width in the process image 8 outputs
Electrical isolation channels/control voltage: no, between the channels: no, control voltage/fieldbus: yes, via IP-Link
Operating/storage temperature 0…+55 °C/-25…+85 °C
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 65/66/67 (conforms to EN 60529)/variable
Approvals CE, UL