2-channel serial interface RS232, D-sub connection EL6002
Status LEDs
Serial interface 1
Serial interface 2
Top view
extended temperature range

EL6002 | 2-channel serial interface RS232, D-sub connection

The EL6002 serial interface enables the connection of devices with two RS232 interfaces. The devices connected to the EL6002 EtherCAT Terminal communicate with the automation device via the Coupler. The active communication channel operates independently of the higher-level EtherCAT system in full duplex mode with 300 baud up to 115.2 kbaud. The RS232 interfaces guarantee high interference immunity through electrically isolated signals.

In conjunction with the TwinCAT Virtual Serial COM Driver, the EL6002 can be used as a normal Windows COM interface.

Technical data EL6002
Technology D-sub, 9-pin
Data transfer channels 2
Data transfer rates 300…115,200 baud; default: 9600 baud, 8 data bits, no parity and one stop bit
Interfaces 2 x RS232
Line impedance
Cable length max. 15 m
Providing external supply
Power supply via the E-bus
Distributed clocks
Electrical isolation 500 V (E-bus/signal voltage)
Data buffer 864 bytes receive buffer, 128 bytes transmit buffer
Bit width in the process image 22 x 8 bit input, 22 x 8 bit output, 16 bit control, 16 bit status
Configuration no address setting, configuration via the controller
Current consumption power contacts
Current consumption E-bus typ. 170 mA
Special features
Weight approx. 55 g
Operating/storage temperature -25…+60 °C/-40…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable
Approvals CE, UL, Ex
Accessories  
TS6360 license for using the TwinCAT Virtual Serial COM Driver for Windows and Windows CE platforms
System  
RS485 For further RS485 products please see the system overview.