2-channel analog output terminal 0…10 V, manual/automatic operation KM4602
Top view
Control element
output voltage
manual operation (output 1)
Control element
output voltage
manual operation (output 2)
Manual/automatic
operation (output 1)
Manual/automatic
operation (output 2)
Output 1
Output 2

KM4602 | 2-channel analog output terminal 0…10 V, manual/automatic operation

The analog KM4602 output terminal has two potential-free analog 0 to 10 V outputs. Both are connected internally to common ground. For each channel a switch enables selection between automatic or manual mode. In automatic mode an analog value is issued depending on the process data. With the manual switch settings the value set via the potentiometer is applied to the output. For manual mode a 24 V supply is required for the Bus Coupler. The switch state can be read by the controller.

Technical data KM4602
Technology single-ended
Number of outputs 2
Power supply via the K-bus
Signal voltage 0…10 V
Load > 5 kΩ (short-circuit-proof)
Output error < ±0.1 % (relative to end value)
Resolution 12 bit
Conversion time ~ 1.5 ms
Electrical isolation 500 V (K-bus/signal voltage)
Current consumption power contacts – (no power contacts)
Current consumption K-bus typ. 175 mA
Configuration no address or configuration setting
Special features manual/automatic operation
Weight approx. 85 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable
Approvals CE
Further manual operating terminals
KM1644 4-channel manual operation
KM2604 4-channel relay module 230 V AC, 16 A, potential-free change-over contact
KM2614 4-channel relay module 230 V AC, 16 A, potential-free change-over contact, with manual operation
KM2642 2-channel relay module 230 V AC, 6 A, manual/automatic operation, relais state readable
KM2652 2-channel relay module 230 V AC, 6 A, manual/automatic operation, switch and relay state readable