Potential supply terminal, 24 V DC, with diagnostics KL9110
Power LED
Power contact
Power contact
Power contact
Infeed 24 V
Infeed 0 V
PE
Top view 
Contact assembly 
extended temperature range
extended shock and vibration range

KL9110 | Potential supply terminal, 24 V DC, with diagnostics

The KL9110 power feed terminal makes it possible to set up various potential groups with the standard voltage of 24 V DC. In order to monitor the supply voltage, the terminal with diagnostics reports the status of the power feed terminal to the Bus Coupler through two input bits. It is thus possible for the controller to check the distributed peripheral voltage over the fieldbus.

Technical data KL9110 | KS9110
Nominal voltage 24 V DC
Current load ≤ 10 A
Integrated fine-wire fuse
Diagnostics yes
Power LED green
Defect LED
Reported to K-bus yes
PE contact yes
Shield connection
Connection facility to additional power contact 1
K-bus, looped through yes
Bit width in the process image 1
Electrical connection to DIN rail
Current consumption K-bus typ. 10 mA
Electrical isolation yes
Housing width in mm 12
Weight approx. 50 g
Side by side mounting on Bus Terminals with power contact yes
Side by side mounting on Bus Terminals without power contact yes
Operating/storage temperature -25…+60 °C/-40…+85 °C
Pluggable wiring for all KSxxxx Bus Terminals
Approvals CE, UL, Ex, GL, IECEx