Power terminal for Siemens contactor, series Sirius 3R KL8001
Terminal bus
signal input
400 V AC 3~
mains connection
Diagnostics LEDs
Contactor
connection adapter
Terminal bus
transmission
Manual nominal
current selector

KL8001 | Power terminal for Siemens contactor, series Sirius 3R

Like a standard motor protection relay the KL8001 power terminal is fitted to a power contactor up to a switching capacity of 5.5 kW. The connection mechanism of the KL8001 power terminal of the KL8xxx series is particularly suitable for Siemens contactors of the Sirius 3R series. Other power terminals are adapted for other contactor manufacturers. The power terminal switches the installed contactor and takes over all the functions of the motor protection relay. Apart from its purely protective function of switching off the motor when overloaded, the power terminal can carry out numerous diagnostic functions on the motor and make the information available to the controller via the fieldbus.

Technical data KL8001
Number of power terminals up to 10 (at 140 mA typ. current consumption per contactor)
Contactor connection mechanism for Siemens contactor series Sirius 3R (switch size S00, Typ 3RT 10 1)
Type of connection power path screw terminals up to 2 x 2.5 mm²
Current load max. 25 A (fuse)
Short-circuit-proof up to 5 kA
Internal resistance < 1 mΩ
Setting range of nominal current 0.9…9.9 A
Tripping classes class 5, 10, 15, 20, 25, 30 selectable
Measured values current, voltage, power
Measuring error 0.1 A AC
Measuring voltage 500 V AC
Type of K-bus connection 2 x flat plug socket, 10-pin
Current consumpt. K-bus typ. 150 mA
Current consumption power contacts typ. 7 mA + load
Power contacts 24 V DC (-15 %/+20 %)/1.4 A max., short-circuit-proof
Electrical isolation 500 V (24 V DC/K-bus), 2,500 V (mains supply/K-bus)
Configuration possibility automatically, via the fieldbus, KS2000, rated current also manually
Bit width in the process image input/output: 64 bits, 8 bit control/status, 32 bit data
Adapter terminal KL9060
Short circuit behaviour conforms to EN 60947-4-1 (assignment type 2)/VDE 102
Triggering tolerance conforms to IEC 947, as well as UL and CSA
Weight approx. 90 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable, contactor dependent
Approvals CE
Accessories  
KL9060 Adapter terminal for KL8001 power terminals
ZK1010-8080-3003 ribbon cable for bus connection between two power terminals KL8001, length 0,03 m, included in scope of supply of KL8001
ZK1010-8080-3005 ribbon cable for bus connection between two power terminals KL8001 for reversing contactor connection, length 0,05 m
ZK1010-8080-3010 ribbon cable for bus connection between the KL9060 and the KL8001, length 0,1 m, included in scope of supply of KL9060
ZS1010-1610 Plug for exposed bus connection of the KL8001, included in scope of supply of KL9060
Related products  
KL8601 Communication module for Schneider motor starter TeSys model U