2-channel oscilloscope terminal -10…+10 V KL3362
Error LED1
Output LED
Error LED2
Trigger LED
+24 V
24 V Output
Input 1
Shield
24 V Trigger
0 V
Input 2
Shield
Top view 
Contact assembly 

KL3362 | 2-channel oscilloscope terminal -10…+10 V

The KL3362 analog input terminal makes it possible to perform non-central preliminary processing of analog values. The input values are digitised with a 14 bit resolution and written into an internal memory. An efficient processor can pre-process the values. Limit values and maximum and minimum values can be determined or monitored. The KL3362 can also carry out envelope curve monitoring. A trigger starts the cyclical processes. The result or all the measured values are transported to the higher-level automation unit.

Technical data KL3362 | KS3362
Number of inputs 2 analog, 1 trigger
Power supply via the K-bus
Signal voltage -10…+10 V
Technology high-speed data logger
Internal resistance > 500 kΩ
Internal resistance E1-GND, E2-GND > 500 kΩ
Supply voltage
Conversion time < 100 µs, configurable (10 µs with fast sampling mode)
Resolution 14 bit + sign
Measuring error < ±0.5 % (relative to full scale value)
Internal memory 32 kbytes
Trigger configurable
Current consumption power contacts – (no power contacts)
Current consumpt. K-bus typ. 120 mA
Bit width in the process image input/output: 2 x 16 bit data (2 x 8 bit control/status per channel)
Special features high-speed analog analysis
Weight approx. 55 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable
Pluggable wiring for all KSxxxx Bus Terminals
Approvals CE, UL, Ex