2-channel analog input terminal 0…10 V KL3062
Run LED1
Run LED2
+Input 1
Ground
Shield
+Input 2
Ground
Shield
Top view 
Contact assembly 
extended shock and vibration range

KL3062 | 2-channel analog input terminal 0…10 V

The KL3062 analog input terminal handles signals in the range from 0 to 10 V. The voltage is digitised to a resolution of 12 bits and is transmitted, electrically isolated, to the higher-level automation device. The input channels of the Bus Terminal have a common ground potential, the reference ground. The run LEDs give an indication of the data exchange with the Bus Coupler.

Technical data KL3062 | KS3062
Number of inputs 2
Power supply via the K-bus
Signal voltage 0…10 V
Technology single-ended
Internal resistance > 130 kΩ
Common-mode voltage UCM
Resolution 12 bit
Conversion time ~ 2 ms
Measuring error < ±0.3 % (relative to full scale value)
Electrical isolation 500 V (K-bus/signal voltage)
Current consumption power contacts – (no power contacts)
Current consumption K-bus typ. 60 mA
Bit width in the process image input: 2 x 16 bit data (2 x 8 bit control/status optional)
Configuration no address or configuration setting
Weight approx. 60 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable
Pluggable wiring for all KSxxxx Bus Terminals
Approvals CE, UL, Ex
Special terminals
KL3062-0010 Siemens S5 format
KL3062-0011 voltage level 0…20 V
KL3062-0012 fast µP, scan time approx. 0.5 ms
KL3062-0013 voltage level 0…30 V
KL3062-0014 voltage level 0…50 V
KL3062-0050 Siemens S7 format