2-channel pulse width current terminal ±1 A, 24 V DC KL2535
Error B LED
Warning
Enable B LED
Power LED
Error A LED 
Enable A LED 
Run LED 
Power contact
+24 V
Power contact 0 V
A1
B1
Sense A
Input 1
A2
B2
Sense B
Input 2
Top view 
Contact assembly 

KL2535 | 2-channel pulse width current terminal ±1 A, 24 V DC

The KL2535 output terminal controls an output current via pulse width control of the supply voltage. It is galvanically isolated from the K-bus. The current value (0 to ±1 A) is specified by the automation device via a 16 bit value. The output stage is protected against overload and short-circuit. The Bus Terminal contains two channels that indicate their signal state by means of light emitting diodes. The LEDs simplify local diagnosis by displaying typical load and wiring faults.

Technical data KL2535 | KS2535
Number of outputs 2
Rated load voltage 24 V DC (-15 %/+20 %)
Load type inductive > 1 mH, valves, coils
Max. output current 2 x ±1 A (short-circuit-proof, thermal overload-proof for both channels together)
PWM clock frequency 36 kHz
Duty factor 0…100 % (current-controlled)
Resolution max. 12 bit
Electrical isolation 500 V (K-bus/field potential)
Current consumption power contacts only load
Current consumption K-bus typ. 60 mA
Bit width in the process image 48 inputs/outputs: 2 x 16 bit data, 2 x 8 bit control/status
Configuration no address setting, configuration via Bus Coupler or controller
Weight approx. 55 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/see documentation
Pluggable wiring for all KSxxxx Bus Terminals
Approvals CE
Product announcement
KL2535: available
KS2535: estimated market release on request